The Simoprime Logo

Simoprime Technical Data

Classification of SIMOPRIME switchgear according to IEC 62271-200

Click Here To View Our Simoprime Technology Partner Certification

Electrical data (maximum values) of SIMOPRIME:

RATINGS

Rated values (Max)

Switchgear up to 7.2 kV
Rated voltage 7.2 kV
Rated frequency 50/60 Hz
Rated short-duration power-frequency withstand voltage 20 kV *
Rated lightning impulse withstand voltage 60 kV
Rated short-time withstand current, 3 s 40 kA
Rated peak withstand current at 50/60 Hz 100/104 kA
Rated short-circuit breaking current 40 kA
Rated short-circuitmaking current at 50/60 Hz 100/104 kA
Rated normal current of busbar 3600 A
Rated normal current of feeders
– with circuit-breaker 3600 A
– with vacuum contactor 400 A **

 

 

Switchgear 12 kV

Rated voltage 12 kV
Rated frequency 50/60 Hz
Rated short-duration power-frequency withstand voltage 28 kV *
Rated lightning impulse withstand voltage 75 kV
Rated short-time withstand current, 3 s 40 kA
Rated peak withstand current at 50/60 Hz 100/104 kA
Rated normal current of busbar 3600 A
Rated normal current of feeders
– with circuit-breaker 3600 A
– with vacuum contactor 400 A **

 

 

Switchgear 17.5 kV

Rated voltage 17.5 kV
Rated frequency 50/60 Hz
Rated short-duration power-frequency withstand voltage 38 kV *
Rated lightning impulse withstand voltage 95 kV
Rated short-time withstand current, 3 s 40 kA
Rated peak withstand current at 50/60 Hz 100/104 kA
Rated short-circuit breaking current 40 kA
Rated short-circuitmaking current at 50/60 Hz 100/104 kA
Rated normal current of busbar 3600 A
Rated normal current of feeders
– with circuit-breaker 3600 A
  • * Option: Higher values according to Gost standards
  • ** Depending on the rate of the HV HRC fuses installed
  • *** 60V for vacuum contractor

PERSONAL SAFETY NO 1 PRIORITY!!

Classification, dimensions, room planning

Classification of SIMOPRIME switchgear according to IEC 62271-200

Internal arc classification:

 

Classification

IAC

Accessibility

– Front Type A
– Rear Type A
– Lateral Type A
Test Current kA 25/31.5/40
Arc duration s 0.1/1.0

Construction and design:

Partition class

Loss of service continuity category

PM (metallic partition)

LSC2B (metal -clad)

Compartment accessibility (standard)
Busbar compartment Tool Based
-switching -device compartment interlock-controlled
Low-voltage compartment Tool Based
Connection compartment interlock-controlled and tool-based
-Front connection Tool Based
-Rear Connection Tool Based

 All panel types (Dimensions in mm)

Width B Circuit-breaker panel Up to 31.5 kA 40kA
≤1250 A
2500 A, 3150 A, 3600 A 800 800
Contactor panel 435 2)/600 435 2)
 Disconnecting panel
 ≤1250 A  600  800
 2500 A, 3150 A, 3600 A 800  800
 Bus sectionalizer/circuit-breaker
 panel ≤1250 A  600  800
 2500 A, 3150 A, 3600 A  800  800
 Bus sectionalizer/bus riser panel
≤2500 A  600  800
 3150, 3600 A  800  800
 Metering panel  600  800
 Height  H1 With standard low-voltage compartment and IAC 0.1s  2253  2253
H2 With standard low-voltage compartment and IAC 1.0s  2425  2460
 H3 _  1780  1780
 Depth  Standard  1860  1860

Rear Connection

Single – row arrangement  (plan view)

For dimensions B (width) and T (depth) refer to table on this page

1) Control aisle widths:

≤31.5 kA andw3150 A versions: ≥1500mm
40 kA or 3600 A versions: ≥1700mm
For panel replacement: ≥2000mm

Standards

Standards, Specifications & Guidelines

The switchgear complies with the relevant standards and specifications applicable at the time of type tests.

Dielectric strength – The dielectric strength is verified by testing the switchgear with rated values of short duration power- frequency withstand voltage and lightning impulse withstand voltage according to IEC 62271-1/VDE 0671-1 (see table“Dielectric strength”).

The rated values are referred to sea level and to normal atmospheric conditions (1013 hPa, 20 °C, 11 g/m3 humidity in accordance with IEC 60071/ VDE 0111).

The dielectric strength decreases with increasing altitude. For site altitudes above 1000 m (above sea level) the standards do not provide any guidelines for the insulation rating. Instead, special arrangements apply to these altitudes.

Site altitude – As the altitude increases, the dielectric strength in air decreases due to the decreasing air density. This reduction is permitted up to a site altitude of 1000 m according to IEC and VDE.

– For site altitudes above 1000 m, a higher insulation level must be selected. It results from the multiplication of the rated insulation level for 0 to 1000 m with the correction factor Ka.

Example: 1800msite altitude above sea level 12 kV switchgear rated voltage 75 kV rated lightning impulse withstand voltage Rated lightning impulse withstand voltage to be selected 75 kV · 1.10 = 82.5 kV

Overview of standards (March 2012)

 

   

IEC standard

VDE standard

EN standard

Switchgear SIMOPRIME IEC 62271-1 VDE 0671-1 EN 62271-1
IEC 62271-200 VDE 0671-200 EN 62271-200
Devices Circuit-breaker IEC 62271-100 VDE 0671-100 EN 62271-100
Vacuum contactor IEC 62271-106 VDE 0670-501 EN 60440
Disconnector and earthing switch IEC 62271-102 VDE 0671-102 EN 62271-102
HV HRC fuses IEC 60282 VDE 0670-4 EN 60282
 Voltage detecting systems  IEC 61243-5  VDE 0682-415  EN 61243-5
 Degree of protection  –  IEC 60529  VDE 0470-1  EN 60529
 Insulation  –  IEC 60071  VDE 0111 EN 60071
 Instrument transformers  Current transformer IEC 61869-1

IEC61869-2

 VDE 0414-1

EN 60044-1

 Voltage transformer  IEC 61869-1  VDE 0414-2  –
 IEC61869-3  –  EN 60044-2
 Installation  –  IEC 61936 –  VDE 0101  –

 Table – Dialectric strength

 

 

 Rated voltage (rms value)  kV  7.2  12  15  17.5
 Rated short-duration power-frequency withstand voltage (rms value)
 – Across isolating distances  kV  23  32  39 45
 – Between phases and to earth  kV  20  28  35 38
 Rated lightning impulse withstand voltage (peak value)
 – Across isolating distances  kV  70  85  105 110
 – Between phases and to earth  kV  60  75  95 95

Altitude correction ka factor

For site altitudes above 1000m, the altitude correction factor ka is recommended, depending on the actual site altitude above sea level.

Rated short-duration power-freq. withstand volt. to be selected for site altitudes>1000m ≥ Rated short-duration power-frequency withstand voltage up to ≤1000m· Ka Rated lightning impulse withstand volt. to be selected for site altitudes > 1000m ≥ Rated lightning impulse withstand voltage up to ≤1000m· Ka

Type of service location

 

 

The switchgear can be used for indoor installation in accordance with IEC 61936 (Power installations exceeding 1 kV AC) and VDE 0101. Outside lockable electrical service locations at places which are not accessible to the public. Enclosures of switchgear can only be removed with tools. Inside lockable electrical service locations. A lockable electrical service location is a place outdoors or indoors that is reserved exclusively for housing electrical equipment and which is kept under lock and key. Access is restricted to authorized personnel and persons who have been properly instructed in electrical engineering. Untrained or unskilled persons may only enter under the supervision of authorized personnel or properly instructed persons.

Terms

 

 

“Make-proof earthing switches” are earthing switches with short-circuit making capacity according to

  • – IEC 62271-102 and
  • – VDE 0671-102/EN 62271-102

Internal arc classification

  • Protection of operating personnel by means of tests for verifying the internal arc classification
  • Internal arcing tests must be performed in accordance with IEC 62271-200/VDE 0671-200
  • The switchgear complies with criteria 1 to 5 specified in the mentioned standards for the basic version up to 40 kA.
  • Definitions of the criteria: –
    • Criterion 1 Correctly secured doors and covers do not open. Limited deformations are accepted.
    • Criterion 2 No fragmentation of the enclosure. Projection of small parts up to an individual mass of 60 g are accepted.
    • Criterion 3 Arcing does not cause holes in the accessible sides up to a height of 2 m.
    • Criterion 4 Horizontal and vertical indicators do no ignite due to the effect of hot gases.
    • Criterion 5 The enclosure remains connected to its earthing point.

Current-carrying capacity

According to IEC 62271-1/VDE 0671-1 and IEC 62271-200/VDE 0671-200 current carrying capacities refer to the following ambient air temperatures:

  • Maximum of 24-hour mean + 35 °C
  • Maximum + 40 °C

The current-carrying capacity of the panels and busbars depends on the ambient air temperature outside the enclosure. To attain the maximum rated normal currents, the panels are provided with natural or forced ventilation.

Climate and environmental influences

The switchgear may be used, subject to possible additional measures, under the following environmental influences and climate classes:

  • Environmental influences
    • Natural foreign materials
    • Chemically active pollutants
    • Small animals
  • Climate classes
    • 3K3
    • 3K5

The climate classes are classified according to IEC 60721-3-3.

Protection against solid foreign bodies, electric shock and ingress of water

SIMOPRIME switchgear fulfills according to the standards

  • IEC 62271-200
  • IEC 60529
  • VDE 0470-1
  • VDE 0671-200
  • the following degrees of protection:
    • Enclosure: IP 4X, IP 5X (protection against solid foreign bodies)
    • IP X1, IP X2 (protection against ingress of water)
  • Compartments:
    • IP 2X (protection against solid foreign bodies)

Higher degree of protection for enclosure on request.

Product Range

Panel configurations

All rights reserved

 

 

If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.